Track Air Pollution Index, Temperature, Humidity and Static Air Pressure
Environment monitoring sensor, ensure your indoor air quality is healthy for people and machines.
Indoor air quality management is an ever-more-important and overlooked area of business operations. Ensuring healthy employees, as well as healthy machines,minimizes disruption to your business.
This 4-in-1 environmental sensor monitors temperature, humidity, air pollution index, and static air pressure.
Make sure temperature is within acceptable bounds with customized thresholds. In a data center, check your server inlet temperatures, in the workplace, ensure OSHA compliance.
Static air pressure measurements in a data center can be used to control fan speeds and ensure correct air supply volumes. Balancing pressures reduces stress to servers, reduces maintenance costs, and fan energy. By subtracting measurements of two static air pressure sensors, a differential pressure is calculated. Use this to check pressure differences before and after transition points. Large pressure differences can signal issues such as blocked air filters.
The air pollution index tracks multiple pollutants, including CO2, NOx, and VOCs, and produces an air quality score. Monitor this over time and ensure the air quality score is stable or decreasing, as an increasing score signifies decreasing air quality.
| Feature | Specification |
| Air Pollution (Gas Sensor) | |
| Output Metric | Air Pollution Level (%) |
| Measurement Range | 0% to 100% |
| Pollution Mapping Logic | |
| Clean Air (0%) | Gas Resistance ≥ 50 kΩ |
| Normal to Warning (0-65%) | 50 kΩ > Resistance > 18 kΩ |
| Warning to Critical (65-85%) | 18 kΩ ≥ Resistance > 5 kΩ |
| Critical to Max (85-100%) | 5 kΩ ≥ Resistance > 1.5 kΩ |
| Max Pollution (100%) | Gas Resistance ≤ 1.5 kΩ |
| Air Pressure | |
| Measurement Range | 300 to 1100 hPa |
| Absolute Accuracy | ±0.5 hPa |
| Relative Accuracy | ±0.05 hPa |
| Temperature | |
| Measurement Range | -40°C to +85°C |
| Measurement Resolution | 0.1°C increments (0.2°F increments) |
| Accuracy | ±0.5°C (at 25°C) |
| Humidity | |
| Measurement Range | 0 to 100% RH |
| Accuracy | ±3% RH (typical) |
| Measurement Resolution | 1% RH increments |
| Hardware Specifications | |
| Max Cable Length | 30m (100ft) Ships with fixed length 4.6m (15ft) as standard. Custom lengths available. |
| Sensor Count | 4 |