The airflow sensor is not a precision measuring instrument. This device is meant to measure the presence or the absence of air flow. The placement of the sensor is very … Read More
Can AKCP provide me with CE certifications for your sensors?
Yes, we have CE certificates for most of our products. You can request them from the AKCP Sales Team at [email protected], or you can download them from our web site. … Read More
What is the internal impedance of your DC Voltmeter sensors?
Our Digital Volt meter has an input impedance of 2M ohms (2,000,000 ohms).
Do you have any sensor that is capable of reading the fluctuation of electricity, and send me reports?
How to monitor electricity fluctuations? We have a sensor that is capable of monitoring Voltage, Wattage and Amperage. This is our Power Meter Sensor. You can set alerts as with … Read More
I see you have two types of temperature and the dual temperature humidity sensors, can I extend both of them?
Yes, we offer two types of these sensors. The TMP01 and THS01 are the fixed one foot type and are only designed to be connected directly to the AKCP base … Read More
If I do extend the run length of my sensors, for example my temperature/humidity sensor, does this affect the reading and accuracy of the sensor?
Does extending the sensor will it affect the reading? All temperature and humidity communications are 100% digital with no loss of accuracy regardless of the length. There is an A/d … Read More
Do I have to use a special type of cable to extend the run length of my sensors?
You can use any type, or brand of standard CAT5/6 UTP LAN cable to extend your sensors.
I have one of you DC Voltmeter sensors and my question was can this sensor handle DC signals from 0 to 10 mV?
What is the resolution of the AKCP DC Voltmeter? The lowest signal will be 0.1V (100mV). We display only the one decimal place in the web interface of the unit. … Read More
I just finished a calibration process, but the reading is still a little bit off. Is there any way to fine tune the reading?
In the calibration process, we set the offset of the reference voltage so that the raw analog read 500 when the input to the RJ45 port is 1.25 volts. However, … Read More
I am sure that all settings for the Digital Voltmeter sensor are correct, but it seems to have error in the reading. How can I correct this error?
The Digital Voltmeter and 4-20mA sensors have an input as analog signal which will be converted to digital using an A/D converter. Normally, the A/D converter is calibrated in production … Read More